EasyManua.ls Logo

Trane TR200 - How to Connect a PC to the Frequency Converter

Trane TR200
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTE
To achieve the highest accuracy with the slip compensation, an Automatic Motor Adaptation (AMA) should be per-
formed. To be enabled in par.1-29
Automatic Motor Adaptation (AMA).
NOTE
Trip will not be active when using a normal stop or coast command.
1-86 Trip Speed Low [RPM]
Range: Function:
0 RPM* [Application dependant] If the trip speed is set to 0, the function is not active.
If the speed after the start (or during a stop) falls below the value in the
parameter at any time, the drive will trip with an alarm [A49] Speed Limit.
Function at stop.
NOTE: This parameter is only available if par.0-02
Motor Speed Unit is set to [RPM].
1-87 Trip Speed Low [Hz]
Range: Function:
0.0 Hz* [Application dependant] If the trip speed is set to 0, the function is not active.
If the speed after the start (or during a stop) falls below the value in the
parameter at any time, the drive will trip with an alarm [A49] Speed Limit.
Function at stop.
NOTE: This parameter is only available if par.0-02
Motor Speed Unit is set to [Hz].
1-9* Motor Temperature
Parameters for setting the temperature protection features for the motor.
1-90 Motor Thermal Protection
Option: Function:
The adjustable frequency drive determines the motor temperature for
motor protection in two different ways:
Via a thermistor sensor connected to one of the analog or digital
inputs (par.1-93
Thermistor Source).
Via calculation (ETR = Electronic Thermal Relay) of the thermal
load, based on the actual load and time. The calculated ther-
mal load is compared with the rated motor current I
M,N
and
the rated motor frequency f
M,N
. The calculations estimate the
need for a lower load at lower speed due to less cooling from
the fan incorporated in the motor.
[0] No protection If the motor is continuously overloaded and no warning or trip of ad-
justable frequency drive is wanted.
[1] Thermistor warning Activates a warning when the connected thermistor in the motor reacts
in the event of motor overtemperature.
[2] Thermistor trip Stops (trips) the adjustable frequency drive when the connected ther-
mistor in the motor reacts in the event of motor overtemperature.
Parameter Description
TR200 Programming Guide 4-31

Table of Contents

Other manuals for Trane TR200

Related product manuals