FMS-2000M
LIT-12013580
26
Technical specications
Specication Description
Intended use Indoor use
Overvoltage category II
Altitude Up to 2000 m
Pressure range 
Alarm range 
Display range 
Accuracy ± 0.5% full scale
Air flow sensor type Digital differential pressure sensor features no offset, zero drift and is hysteresis free
Displayed pressure resolution 
Monitoring capability Up to 4 independent spaces
I/O Resources One digital input for a door switch for each remote pressure sensor
One remote monitoring output for each remote pressure sensor
Operating temperature 32°F to 104°F (0°C to 40°C)
Operating humidity 10% to 95% relative humidity, non-condensing
Mounting Thin mount for shallow wall cavities
Surface mount for FMS-1655 RMA only
Alarm indication 360° Safety Halo color coded visual, audible alarm
Alarm silence Touchscreen, auto-reset
Password protection Up to 50 user passwords with 2 access levels (administrator and restricted)
Communications protocol BACnet MS/TP (to BAS) 76.8k, 38.4k, 19.2k, 9600 baud
Power requirement 24 VAC (nominal, 21.6 VAC minimum/26.4 VAC maximum), 50/60 Hz 30 VA power supply, Class 2,
Limited Energy, or LPS isolated power supply
Power consumption 30 VA maximum
Optional input power supply Universal 120 VAC/240 VAC-to-24 VAC, 30 VA step-down isolation transformer
24 VAC-to-24 VAC, 30 VA isolation transformer
Pollution degree 2
Display resolution 720 pixels x 1280 pixels
Pluggable screw terminal blocks 
Display dimensions
(height x width x depth)
5.3 in. x 3.5 in. x 1.17 in. (134.62 mm x 88.9 mm x 29.72 mm)
Mounted depth Thin mount: 0.58 in (14.73 mm)
Surface mount: 1.17 in (29.72 mm)
Power supply enclosure dimensions
(height x width x depth)
5 in. x 4.7 in. 2.3 in. (127 mm x 119.38 mm x 58.42 mm)
Compliance United States UL Listed to UL 61010-1; FCC 47CFR Part 15; BTL Listed
Canada cUL Listed to CAN/CSA C22.2 NO. 61010-1; ICES-003
Europe CE (EMC Directive) to EN 61326-1
Australia and New
Zealand
RCM Mark (Australian Radiocommunications Act) to EN 61326-1