Manual x/e-touchPANEL 02 | 01-2021 | 2.9 | en
Emergency Application
c
34 / 118
5.
6.
7.
Test Failure, Case 1:
Test could not be performed
within 24 hours.
Test Failure, Case 2:
Function test was performed.
But the previous duration test
ended with an error (failed to
reach full operating time)
which hasn't been corrected.
Click on the Next error symbol to jump to the next error entry.
To test a single emergency unit, click on the respective emergency unit in the Test column
...
Duration test was interrupted_
Battery was not fully charged
because of power failure
_
Charge
battery for at
least 20
hours and
start
duration test
manually
_
Even if the function test is
performed successfully, the
x/e-touchPANEL shows the error
message !T to signal that the error
detected during the last duration
test has not been corrected.
_ Replace
battery and
perform
operation
test
manually.
_
I NOTICE
If a fault has been eliminated, this must be verified by performing a test on this emergency unit. If a battery
was replaced, the test cannot be performed until 24 hours later because the battery needs to be fully charged
for testing
I NOTICE
mains If a function or duration test was interrupted by a failure, the x/e-touchPANEL remembers this.
After the power supply has been restored, the x/e-touchPANEL automatically starts the test again.