The showerhead or other approved Triton device
MUST be regularly cleaned to remove scale and debris.
If it is intended to operate the shower in areas of hard
water (above 200 ppm temporary hardness), a scale
inhibitor may have to be fitted. For advice on the Triton
scale inhibitor, please contact Customer Service.
DO NOT operate the Digital Mixer Processor unit
outside the guidlines as laid out in ‘site requirements’
and ‘specifications’.
DO NOT connect to a combination cylinder unless the
minimum cold storage can be achieved as the shower
can deliver up to 16 litres/min.
DO NOT connect the low pressure Digital Mixer
Processor unit to the mains water supply as this would
damage the unit.
When installed, the top of the low pressure Digital
Mixer Processor unit MUST be at least 100 mm lower
than the base of the cold water cistern to prevent the
unit running dry.
A dedicated cold water supply MUST be taken directly
from the cold water cistern to the low pressure Digital
Mixer Processor unit.This draw-off MUST be on the
opposite side of the cistern to the float operated valve
to reduce the risk of air entering the unit.
The infill to the cistern should be checked to ensure an
adequate infill rate occurs.