Trox FKRS-EU - Installation: Lightweight Partition Walls (Cladding Both Sides); Requirements for Cladding Both Sides

Trox FKRS-EU
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.6
Lightweight partition walls
□ A
□ A1
12,5
C-C
12,5
a ≥10
W ≥100
≤ 625
□ A1
□ A1
□ A1
C
C
Y
Z
Y
Z
X
X
X
①*
①*
①*
①*
②*
①*
Fig. 16: Lightweight partition wall with metal support structure and cladding on both sides
UW section
CW section
Screw or steel rivet
Double layer cladding, on both sides of the metal
stud system
Mineral wool (depending on wall construction)
Dry wall screw
Trim panels, according to the installation details
Fold the tab inward or cut it off
* closed end must face installation opening A
Requirements
Lightweight partition walls with metal support structure and cladding on both sides, with European classification
to EN 13501-2 or equivalent national classification
Cladding on both sides made of gypsum bonded or cement bonded panel materials or fibre-reinforced gypsum,
wall thickness W ≥ 100 mm
≤ 625 mm distance between metal studs
The installation opening must be stabilised with a reinforcing section or with horizontal and vertical sections
Additional layers of cladding or double stud systems are approved
Duct connection with flexible connector (recommended)
Installation
Lightweight partition walls
Fire damper Type FKRS-EU 27