8
Functional test
General
During operation at normal temperatures, the damper
blade is open. A functional test involves closing the
damper blade and opening it again.
8.1
Fire damper with fusible link
Closing the damper blade
Fig. 40: Closing the damper blade
CAUTION!
Danger of injury when reaching into the fire damper
while the damper blade is moving. Do not reach into
the fire damper while actuating the release mecha-
nism.
Requirement
The damper blade is OPEN
1. Grasp the release mechanism as shown with
the thumb and middle fingers.
2. Pull the release mechanism towards you with both
fingers.
ð
The damper blade closes and the tab on
the handle locks into the CLOSED position.
Opening the damper blade
Fig. 41: Opening the damper blade
Requirement
The damper blade is CLOSED
1. With your left hand, pull the release mechanism
towards you and hold it.
2. With your right hand, grasp the handle as
shown and press down the tab with your
thumb.
3. Then turn the handle anti-clockwise to the travel
stop.
4. Release the mechanism.
ð
The handle locks into the OPEN position.
Damper blade position indicator
The position of the damper blade is indicated by the
position of the handle.
Functional test