EasyManua.ls Logo

Trox FKRS-EU - Maintenance: Replacing the Fusible Link; Removing the Fusible Link Holder; Replacing the Fusible Link

Trox FKRS-EU
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.3
Replacing the fusible link
Fig. 49: Removing the fusible link holder
1. Close the damper blade.
2. Release screws on the fusible link holder .
3. Remove fusible link holder from the fire
damper. While doing so, slightly press down the
tab of the handle.
1.
2.
Fig. 50: Removing the fusible link holder
4. Grasp the fusible link holder as shown. Move your
middle fingers into the direction of the arrow.
5. Remove the used fusible link.
6. Insert the new fusible link.
7. Put the fusible link holder back into the fire
damper and fix it with screws .
8. Carry out functional test.
Maintenance
Replacing the fusible link
Fire damper Type FKRS-EU58

Table of Contents

Other manuals for Trox FKRS-EU