Trox FKRS-EU - Maintenance Schedule: Regular and As-Required; Interval B: Regular Checks; Interval C: As Required

Trox FKRS-EU
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Interval Maintenance work Personnel
Function of external smoke detector
Function OK
Fire damper closes when triggered manually or when smoke is
detected
Fire damper opens after reset
Determine and eliminate the cause of the fault
Repair or replace smoke detector
Specialist personnel
C Cleaning the fire damper
No contamination in the interior or on the exterior of the fire damper
No corrosion
Remove contamination with a damp cloth
Remove corrosion or replace part
Specialist personnel
Interval
A = Commission
B = Regularly
The functional reliability of fire dampers must be tested at least every six months. If two consecutive tests are
successful, the next test can be conducted one year later.
C = As required, depending on the degree of contamination
Maintenance work
Item to be checked
Required condition
Remedial action if necessary
Maintenance
Inspection, maintenance and repair measures
Fire damper Type FKRS-EU60