TTL Air curtain systems - control and automation panel type Touch
9. Displays and general operating settings (cont.)
9.2.4 Menue 4 - controller air temperature (AIR controller)
OK
Cancel
blow-out temperature
controller AIR P-rate
controller AIR I-rate
wasser target standby
1
2 3
4
5 6 7 8 9 1
1
2
45 °C
setting in
1 °C steps
/controller air temperature/wasser target sta
OK
Cancel
blow-out temperature
controller AIR P-rate
controller AIR I-rate
wasser target standby
1
2 3
4
5 6 7 8 9 10
1
2
32 °C
setting in
1 °C steps
/controller air temperature/wasser target standb
4 Controller air temperature menue 1 - wasser target standby
setting of a water temperature to be hold in standby mode.
It is necessary for start or restart of unit and the thereby
achieving blow-out temperature
4 Controller air temperature menue 2 - blow-out temperature
setting of a blow-out temperature to achieve or to hold by
controller operation
OK
Cancel
blow-out temperature
controller AIR P-rate
controller AIR I-rate
wasser target standby
1 2 3 4 5 6 7 8 9 10
1
2
1
controller AIR P-rate
0 = Off
255 = max
/controller air temperature/wasser target standb
5 Controller air temperature menue 3 - controller AIR P-rate
Controller K
p
SURSFRQWUROOHUDPSOLÀFDWLRQ
controller parameter for adaption of control characteristic
7KHPRGLÀFDWLRQDIIHFWVGLUHFWO\WKHFRQWUROOHUVEHKDYLRXUDQG
should be changed only after consultation with TTL service!
OK
Cancel
reduction blow out temperature
controller AIR I-rate
controller AIR D-rate
controller AIR summer release
controller AIR P-rate
1 2 3 4 5 6 7 8 9 10
1
2
1
controller AIR I-rate
0 = Off
255 = max
/controller air temperature/contr. AIR I-rate
5 Controller air temperature menue 4 - controller AIR I-rate
Controller K
i
LQWHJUDOFRHIÀFLHQW
controller parameter for adaption of control characteristic
7KHPRGLÀFDWLRQDIIHFWVGLUHFWO\WKHFRQWUROOHUVEHKDYLRXUDQG
should be changed only after consultation with TTL service!
OK
Cancel
reduction blow out temperature
controller AIR I-rate
controller AIR D-rate
controller AIR summer release
controller AIR P-rate
1
2 3
4
5 6 7 8 9 10
1
2
1
controller AIR D-rate
0 = Off
255 = max
/controller air temperature/contr. AIR D-rate
5 Controller air temperature menue 5 - controller AIR D-rate
Controller K
d
GLIIHUHQFLDOFRHIÀFLHQW
controller parameter for adaption of control characteristic
7KHPRGLÀFDWLRQDIIHFWVGLUHFWO\WKHFRQWUROOHUVEHKDYLRXUDQG
should be changed only after consultation with TTL service!
OK
Cancel
controller AIR summer release
reduction blow-out temperature
reduction start temperature
controller AIR D-rate
1 2 3 4 5 6 7 8 9 10
1
2
OFF
controller mode
summer
/contr. AIR temperature/contr. AIR summer relea
5 Controller air temperature menue 6 - controller AIR summer rel.
activation of air temperature controller (AIR)
for summer operation