TVL 351
ISSUE 15
Code-076 CONTROL SGL **Brown Out Reset***.
Brown Out Reset, The internal CPU has reset due to a brown out on it's power supply.
[Fault]
Code-077 CONTROL SGL ***External Reset***.
Reset push has been pressed, The internal CPU has detected the NRST signal go low.
[Fault]
Code-078 CONTROL SGL ***Power on Reset***.
Power on reset, The mains supply has been removed from more than 1 second, check supply wiring or fuses, riser
supply.
[Information]
Code-079 CONTROL SGL **Low Power Reset***.
Low power reset, The internal CPU has had a low power reset.
[Fault]
Code-080 MOTION SGL Emergency Slowdown.
Emergency slowdown. The lift was over speeding as it came into the terminal floor or had a fault that required
immediate slowdown, check BFR/TFR/DZ switches, encoders and slowing points / setup.
[Fault]
Code-081 DRIVE SGL MC Lost On Start.
MC feedback lost on starting, check safety circuit/terminal limits, motor overload contacts and drive start settings.
[Fault]
Code-082 DRIVE SGL MC Lost On Stop.
MC feedback lost on stopping sequence, check brake set timing, drive stopping sequence and safety circuit/terminal
limits.
[Fault]
Code-083 MOTION MAN Multi Head Error / Multi Head Reset.
Leveller error on 3 accumulated journeys, check tape head signals (LU/LD/DZ,DZM). Clear fault in toolbox menu.
[Breakdown]
Code-084 MOTION SGL Fail To Leave Floor.
Lift has failed to leave floor, check drive if stalled. Status of LU/LD has not changed after set time. Three of these
events will give a Multi Start Fail code 014. The Factory defaults for the Escape Floor Time are 2.1 seconds for lifts
running at 1m/s or greater, otherwise it is set at 4.2 seconds.
[Fault]
Code-085 MOTION SGL Start Leveller Or Direction Error.
Leveller or direction error on start, check signals (LU/LD), check brake settings for rollback and associated start
timers.
[Fault]
Code-086 CONTROL SGL RTC Time Set.
The real time clock time has been set to a new value by the User.
[Information]
Code-087 CONTROL SGL RTC Date Set.
The real time clock date has been set to a new value by the User.
[Information]
Code-088 MOTION SGL Lift Is LOST.
lift is lost due to position data being not valid, check shaft positioning equipment, shaft encoder settings. Lift will dive
on next journey
[Fault]
Code-089 MOTION SGL Re-Level Timeout.
Lift failed to re-level after 5 seconds, check levellers (LU/LD) and drive settings.
[Fault]