TVL 351
ISSUE 15
Code-104 CONTROL DBL Safety Chain Fault / Safety Chain OK.
Check OSG / final limits and emergency stop switches in motor room or shaft. This event will occur with a lost LAR
and TTR, check previous events to see if this is the case.
[Breakdown]
Code-105 CONTROL DBL Main Power Failed / Main Power OK.
Main power has failed, check PS/TN signals on motherboard.
[Breakdown]
Code-106 DOORS DBL Front Door Jammed / Front Door Jam Cleared.
Front Door Jammed, Check door tracks for blockages or Door gear. Doors have tried to open and close without
finding either of the door limits
[Breakdown]
Code-107 DOORS DBL Rear Door Jammed / Rear Door Jam Cleared.
Rear Door Jammed, Check door tracks for blockages or Door gear. Doors have tried to open and close without
finding either of the door limits
[Breakdown]
Code-108 MOTION MAN LU/LD/DZ Lost Stopped / LU/LD/DZ Stopped OK.
Leveller and Door Zone Signals lost when stopped, check LU, LD and DZ signals and head supply. Fault will need a
manual reset via the button in the corresponding event in solutions menu.
[Breakdown]
Code-109 CONTROL DBL CAN1 Bus Off / Error Passive / CAN1 Bus On / Bus OK.
The CAN1 Controller (Group Net.) is not transmitting. Check termination resistors are correct, check baud-rate and
wiring.
[Fault]
Code-110 DOORS DBL Front Door Close Fault / Front Door Close OK.
Front Door Close Fault, Check for Door obstructions, Door Tracks, Check door limits / locks / door operation.
[Breakdown]
Code-111 DOORS DBL Rear Door Close Fault / Rear Door Close OK.
Rear Door Close Fault, Check for Door obstructions, Door Tracks, Check door limits / locks / door operation.
[Breakdown]
Code-112 CONTROL SGL Number Of Floors Capped.
Number of floors defined by risers and call collective exceeds working limit, levels have been restricted to those that
can be served. Group highest is lower than lift's top floor
[Fault]
Code-113 CONTROL DBL Low Pressure Shutdown / Low Pressure OK. .
Low Pressure has been detected. The lift has returned to the bottom floor and shut down.
[Breakdown]
Code-114 SERVICES DBL 95% Bypass / Off 95% Bypass.
Lift is on Bypass and will not accept any more landing calls until load drops below target. If no car calls present lift
will park with doors open after answering the last car call in system
[Information]
Code-115 SERVICES MAN Test Up Limit Operated / Test Up Limit OK.
Test Up Limit Signal Missing or Shorted! Lift will not move when next on test. The fault must be cleared from the
'Solutions' menu
[Breakdown]
Code-116 CONTROL DBL Step Comms Fail / Step Comms Restore.
In-House testing - Communication Issue between Step and the Ethos
[Information]