Code-131 MOTION MAN Missing BFR/TFR / Missing B/TFR cancel.
Lift travelled full length of the shaft, BFR/TFR not seen, check switch operation and inputs. Clear fault via button in
the 'Solutions' menu.
[Breakdown]
Code-132 SERVICES DBL AutoRun Enabled / AutoRun Disabled.
AutoRun has been enabled to run the lift and answer calls, or disabled due to problems encountered, check events.
[Service]
Code-133 MOTION SGL GL|CG Lost Test Speed.
GL or CG lost on Test Speed, check lock circuits and skates etc. for floor indicated by event.
[Fault]
Code-134 CONTROL SGL Trace Triggered.
The event trace has been stopped by detecting the trace event.
[Information]
Code-135 DOORS SGL Gate Lock Short Check.
Potential gate lock short, processor is checking the doors by cycling, 3 times gives a Gate Lock Bridged.
[Fault]
Code-136 MEMORY SGL Parameter SD1 Write Pass.
Parameter data has been written to card SD1
[Information]
Code-137 MEMORY SGL Parameter SD1 Write Fail.
Parameter data not copied to SD1. Check valid card is inserted into slot SD1 and the card has not been
disconnected via toolbox menu.
[Fault]
Code-138 MEMORY SGL User Import Fail.
User data held on card SD1 has not been copied to Ethos Two. Is card SD1 missing or corrupt? Does the card
contain factory and user parameter files?
[Fault]
Code-139 MOTION SGL Re-level Error.
Lift failed to achieve level after re-level attempt, check levellers (LU/LD) and drive settings.
[Fault]
Code-140 SERVICES SGL Anti-Nuisance.
Car calls were cancelled because no passengers were detected as entering the lift, check safety edge device.
[Information]
Code-141 DOORS DBL Front Door Limit Error / Front Door Limits OK.
Front Door Limit Error, Both Limits have been seen at the same time, check limit operation and inversion settings.
[Breakdown]
Code-142 SERVICES SGL AutoRun Passed.
AutoRun has successfully completed it's task with no faults stopping it's operation.
[Information]
Code-143 SERVICES SGL AutoRun Failed.
AutoRun has been terminated by the system due to a fault / event with the elevator. Check events preceding this
one.
[Fault]
Code-144 SERVICES SGL AutoRun Terminated.
AutoRun has been terminated by the user, through the autorun setting or via the help key being pressed.