TVL 351
ISSUE 15
Code-145 MOTION SGL BFR/TFR DIR Error.
Incorrect BFR or TFR sequence. Lift could be travelling in the wrong direction. Check motor wiring and phases.
[Fault]
Code-146 CONTROL DBL CAN1 Duplicate ID / CAN1 Bus OK.
A duplicate id has been received from the CAN1 bus this controller has gone off line.
[Fault]
Code-147 CONTROL SGL SMS Status Request.
An SMS lift status request has been received. An SMS containing basic lift status will be sent back to the originator.
[Information]
Code-148 CONTROL SGL Modem Init, Error.
The modem has not initialised correctly. Check modem power and serial communications cables.
[Fault]
Code-149 SERVICES DBL Valve Test Return / Off Valve Test Return.
Lift is on valve test return service, so we can test the valves, once every 24hrs.
[Service]
Code-150 SERVICES DBL On Bus Stop / Off Bus Stop.
The car is on bus stop service. A pattern of landing calls will be entered automatically to provide a limited level of
service. This event is normally preceded by lost push feed or dispatch failure events. Check the push feed supplies
LPF/CPF and /or dispatcher communications..
[Service]
Code-151 SERVICES DBL Dispatcher Master / Dispatcher Slave.
Indicates a change in dispatcher status. The master dispatcher is responsible for dispatching landing calls for all
cars.
[Information]
Code-152 SERVICES SGL Riser Time-Out.
Landing calls have been cancelled. Cars are in group but have been unable to service landing calls for 2 minutes,
check WS95.
[Fault]
Code-153 MOTION DBL Multi LTLR Trip / Multi LTLR Reset.
3 Low Speed Time-outs have occurred, check levellers, check for motor stall, check drive torque settings or LTLR
timer.
[Breakdown]
Code-154 SERVICES DBL Emergency Supply Return / Off Emergency Supply Return.
Lift is on Emergency Supply Return Service.
[Service]
Code-155 MEMORY DBL Group CRC mismatch / Group CRC OK.
GDT stamp matches but CRC's do not, problem with network data. Check templates are same.
[Fault]
Code-156 SERVICES DBL No Duty Car ESUP / Duty Car ESUP OK.
Lift is on emergency supply but is no duty car, check duty car settings.
[Breakdown]
Code-157 MEMORY DBL Group Template Problem / Group Template OK.
Group data needs updating but templates do not match. Check software builds.
[Fault]
Code-158 CONTROL DBL Landing Network Fault / Landing Network OK.
The serial landing network has a problem, check landing node alive screens.
[Fault]