Page 42 of 102
TVL 351
ISSUE 15
Code-231 MOTION DBL Seek Next Floor Up / Seek Floor Up Found.
The lift is moving to the next floor, in the up direction.
[Information]
Code-232 MOTION DBL Parking / Parking End.
The car is homing (parking) to a predefined floor level after a period of idleness.
[Information]
Code-233 DOORS DBL Front Door Lock Test Request / Front Door Lock Test Complete.
The front door lock circuitry is being tested. Also known as a Preflight check.
[Information]
Code-234 DOORS DBL Rear Door Lock Test Request / Rear Door Lock Test Complete.
The rear door lock circuitry is being tested. Also known as a Preflight check.
[Information]
Code-235 MOTION MAN Manual Events Reset / Manual Events Reset Acknowledged.
All manually resettable events have been restored, this event must be acknowledged. Button to reset can be found
in the Solutions screen
[Breakdown]
Code-236 SERVICES DBL Awaiting Car Call / Car Call Pressed.
Fault active that requires car call to try to put the lift back in service, press any car call.
[Breakdown]
Code-237 CONTROL DBL SD1 Card Absent / SD1 Card Detected.
SD1 card is missing, please insert a micro SD card into slot SD1. Without a card event data will not be recorded
[Information]
Code-238 CONTROL DBL SD1 Card Error / SD1 Card Okay.
Card error, User Data field provides card and error code, contact TVC for assistance
[Information]
Code-239 CONTROL SGL SD1 Card Formatted.
The SD1 card was invalid and has successfully been formatted.
[Information]
Code-240 CONTROL DBL SD1 Card Full / SD1 Card Not Full.
SD1 card is full, please make more space available.
[Information]
Code-241 CONTROL DBL Car Network Fault / Car Network OK..
The serial car network has a problem, check car node alive screens.
[Fault]
Code-242 MOTION SGL Contactor Mon.Stuck.
The main MC or STR Contactor maybe stuck in, check contactor or wiring.
[Fault]
Code-243 MOTION SGL LTLR Tripped.
Low Speed Time Out has timed, check levellers, check for motor stall at low speed, check drive torque settings or
LTLR timer.
[Fault]
Code-244 CONTROL DBL Hyd Thermal Recall / Off Hyd Thermal Recall.
Motor room temperature sensor has tripped, car will recall to bottom floor.
[Service]
Code-245 CONTROL MAN Top Final Shutdown / Top Final Limit Reset.
Up Terminal Auxiliary Limit Operated. Lift over travelled and was shut down!
[Breakdown]