YK10-0015-DI-002-03
20
Table. 3 Electric capacity of standard motor and selection criteria for protector
Model
Motor
power kW
(*1)
Voltage - Frequency
Rated
current
A
Starting
current
A
Molded
Case
Circuit
Breaker
A
Thermal
relay
A
(*2)
Power
cords mm
2
PMB-040C
15
200V
class
motor
200V -
50Hz
58.8 484
125
58.8
30
200V -
60Hz
55.6 408 55.6
220V -
60Hz
52.0 449 52.0
230V -
60Hz
50.6 469 50.6
400V
class
motor
400V -
50Hz
29.4 242
100
29.4
22
400V -
60Hz
27.8 204 27.8
440V -
60Hz
26.0 224 26.0
460V -
60Hz
25.3 235 25.3
PMB-060C
18.5
200V
class
motor
200V -
50Hz
74.0 668
125
74.0
30
200V -
60Hz
69.0 524 69.0
220V -
60Hz
65.0 576 65.0
230V -
60Hz
64.0 603 64.0
400V
class
motor
400V -
50Hz
37.0 334
100
37.0
22
400V -
60Hz
34.5 262 34.5
440V -
60Hz
32.5 288 32.5
460V -
60Hz
32.0 301 32.0
*1: 200V class motor and 400V class motor can be selected.
*2: Reference values based on allowable current value of 2PNCT