6
vacon • 34 Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Instance Attribute “Run1”
The data type of this attribute is BOOL. The Attribute Identifier of this attribute is 3
d. This attribute
affects the run/stop behavior of the drive.
Instance Attribute “Run2”
The data type of this attribute is BOOL. The Attribute Identifier of this attribute is 4
d. This attribute
affects the run/stop behavior of the drive.
Instance Attribute “NetCtrl”
The data type of this attribute is BOOL. The Attribute Identifier of this attribute is 5
d
. This attribute
allows the network to request run/stop control to be assigned to the network. If the bit is 0, this
means that run/stop control is local. If the bit is 1, this means that run/stop control is requested to
this network interface.
It should be noted that the actual assignment of run/stop control to this network interface is
reflected in attribute 15
d
.
Table 22.
Class Name Control Supervisor Object
Class Identifier 29
h
Class Attributes Id Name Data Type Access Rule
- - - -
Class Services Id Name
- -
Instance Attributes Id Name Data Type Access Rule
3
h
Run1 Boolean Read-write
4
h
Run2 Boolean Read-write
5
h
NetCtrl Boolean Read-write
6
h
State Unsigned8 Read-only
7
h
Running1 Boolean Read-only
8
h
Running2 Boolean Read-only
9
h
Ready Boolean Read-only
0A
h
Faulted Boolean Read-only
0B
h
Warning Boolean Read-only
0C
h
FaultRst Boolean Read-write
0D
h
FaultCode Unsigned16 Read-only
0F
h
CtrlFromNet Boolean Read-only
Instance Services Id Name
5
h
Reset
0E
h
Get_Attribute_Single
10
h
Set_Attribute_Single