vacon • 60 Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6.3.3 Mapping of Standard Output Assemblies onto Vacon data
This section specifies how data in the Standard Output Assemblies are mapped into Vacon data.
6.3.3.1 FBFixedControlWord
Bit
Description
0 1
0 Start/Stop Stop request from fieldbus Run request from fieldbus
1 Direction Requested direction is "FOR-
WARD"
Requested direction is
"REVERSE"
2 Fault Reset No action. No action. Rising edge (0->1) =
Active faults, alarms and infos are
reset.
3 Coast Stop Mode Stop mode is unmodified. Stop mode is overridden to
"Coasting".
4 Ramp Stop Mode Stop mode is unmodified. Stop mode is overridden to
"Ramping".
5 Quick Ramp Time Normal deceleration ramp time. Deceleration ramp time is
switched to shorter than normal.
6 Freeze Setpoint Changes in the setpoint value
from fieldbus (FBSpeedRefer-
ence) are taken into use by the
application.
Changes in the setpoint value
from fieldbus (FBSpeedRefer-
ence) are not taken into use by
the application.
7 Setpoint to Zero The setpoint value from fieldbus
is taken from FBSpeedReference.
The setpoint value from fieldbus
is switched to 0. When bit 7 has
the value 1, the setpoint value
from the fieldbus control place
shall be set to 0. This value shall
be interpreted as absolute 0 (not
as Minimum Frequency setting).
8 Request Field-
bus Control
Control Place is as parameterised
in the drive (unchanged).
Control Place shall be overridden
to Fieldbus Control.
9 Request Field-
bus Reference
Source of setpoint value shall be
as parameterised in the drive
(unchanged).
Source of setpoint value shall be
overridden to Fieldbus.
10 Inching 1
11 Inching 2
12 Quick Stop Drive operates as normal. Drive executes quick stop / emer-
gency stop.
13 Reserved
14 Reserved
15 Master connec-
tion state
Offline. Active.