Instance Attribute “MotorType”
Vacon 100 drives support values 3 (Permanent Magnet Synchronous Motor) and 7 (Squirrel Cage
Induction Motor)
Instance Attribute “RatedCurrent”
This attribute allows reading and writing of the motor rated current. The unit of the attribute is 100
milliamperes.
Instance Attribute “RatedVoltage”
This attribute allows reading and writing of the motor rated voltage. The unit of the attribute is 1 volt.
Instance Attribute “RatedFreq”
This attribute allows reading and writing of the motor rated electrical frequency. The unit of the
attribute is 1 hertz.
Instance Attribute “PoleCount”
This attribute allows read only of the number of poles in the motor. The unit of the attribute is 1.
Instance Attribute “Base Speed”
This attribute allows reading and writing of the nominal speed at rated frequency. The unit of the
attribute is 1 RPM.
6.2.2.3 Control Supervisor Object, Class 0x29
Control Supervisor Object provides interface for drive management. For example, user can start/
stop motor with this object.
Table 21.
Class Name Motor Data Object
Class Identifier 28
h
Class Attributes Id Name Data Type Access Rule
- - - -
Class Services Id Name
- -
Instsance Attributes Id Name Data Type Access Rule
3
h
MotorType Unsigned8 Read-write
6
h
RatedCurrent Unsigned16 Read-write
7
h
RatedVoltage Unsigned16 Read-write
9
h
RatedFreq Unsigned16 Read-write
0C
h
PoleCount Unsigned16 Read-only
0F
h
Base Speed Unsigned16 Read-write
Instance Services Id Name
0E
h
Get_Attribute_Single
10
h
Set_Attribute_Single