Communications vacon • 63
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
6
6.3.4.7 Setpoint Reached Indication bit in Vacon FBFixedStatusWord
The “Setpoint Reached Indication” bit 5 in the Vacon FBFixedStatusWord is mapped to the “AtRef-
erence” bit in an Input Assembly which supports this bit.
6.3.4.8 Fieldbus Control indication in Input Assemblies
The selected control place is indicated in Input Assemblies which contain the “CtrlFromNet” bit. If
the control place is assigned to fieldbus then this bit is set to 1, else it is 0.
6.3.4.9 Fieldbus Reference indication in Input Assemblies
The selected reference is indicated in Input Assemblies which contain the “RefFromNet” bit. If
thereference is assigned to fieldbus then this bit is set to 1, else it is 0.
6.3.4.10 FBSpeedReference in percentage
This is the reference 1 to the frequency converter. The allowed scaling is from 0 to 10000. In the
application, the value is scaled in percentage of the frequency area between set minimum and max-
imum frequency.
6.3.4.11 Fieldbus Process Data mapping
The Input Assembly Instances 107, 117, 127 and 137 include a number of ProcessDataOut variables,
which are vendor-specific variables which can be sent from the Vacon 100 drive to the EtherNet/IP
master. There can be up to eight ProcessDataOut variables communicated from the drive. The con-
tents of these variables can be parameterised in the Vacon 100 drive using a feature known as
"Fieldbus Process Data mapping".
The Fieldbus Process Data mapping can be configured in the panel or with Vacon Live under "Pa-
rameters / Fieldbus DataMap". Here can be found eight values by which the contents of the eight
ProcessDataOut variables can be configured. Please refer to the Vacon 100 Application Manual and
the section on Fieldbus Data Mapping for further details.
Table 60.
FBSpeedReference Percentage
00,00 %
10000 100,00 %