EasyManua.ls Logo

Vaillant ecoTEC plus 412 - Page 35

Vaillant ecoTEC plus 412
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8000026412_01 Air/flue pipe installation manual 35
CLICK
2. Slide the connection elbow onto the terminal piece until
you hear it click into place.
45° 45°
3. Set the variable terminal to the required position.
If required, the variable terminal can be rotated 45°
anti-clockwise or clockwise. These setting options
mean that the flue system can be further optimised.
4. Install the horizontal wall duct as described
( Section 5.10) or ( Section 5.11).
5.14.3.4 Installing extensions
1. Install the flue system from the wall connector to the
flue outlet.
Start with the lowest extension.
Allow expansion space of 1 cm in each sleeve.
Ensure that all pipe joints are absolutely leak-tight.
Maintain a minimum clearance of 0.5 mm between
the flue gas terminal and the air inlet.
A
2. Secure the extensions to the wall using the pipe
clamps.
Use one pipe clamp for each extension directly
beside the sleeve.
Upstream of each elbow, install another pipe clamp
on the extension.
Note
If all flue gas terminals are at least 1 m away
from the air inlets, the distance (A) between
two wall ducts must be less than 300 mm.

Table of Contents

Related product manuals