EasyManua.ls Logo

Vaillant ecoTEC plus SERIES - Page 27

Vaillant ecoTEC plus SERIES
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Flue gas installation
Installation and maintenance instructions ecoTEC plus 0020116700_01 27
7
Location
Minimum
dimensions
A
Directly below an opening, air brick, opening win-
dows, etc.
300mm
B Above an opening, air brick, opening window, etc. 300mm
C
Horizontally to an opening, air brick, opening win-
dow, etc.
300mm
D
Below temperature-sensitive building components
e.g. plastic gutters, soil pipes or drain pipes
75mm
E Below eaves 200mm
F Below balconies or car port roof 200mm
G From a vertical drain pipe or soil pipe 150mm
H From an internal or external corner 200mm
I Above ground, roof or balcony level 300mm
J From a surface facing the terminal 600mm
K From a terminal facing the terminal 1200mm
L
From an opening in the car port (e.g. door, win-
dow) into the dwelling
1200mm
M Vertically from a terminal on the same wall 1500mm
N Horizontally from a terminal on the same wall 300mm
O From the wall on which the terminal is mounted N/A
P From a vertical structure on the roof N/A
Q Above intersection with roof 300mm
7.1 Position of the termination in a fan-assisted air/flue gas
duct
BS5440–1 It is recommended that the fanned flue terminal
should be positioned as follows:
a) at least 2 m from an opening in the building directly
opposite, and
b) so that the products of combustion are not straightly
directed to discharge across a boundary.
1) Dimensions D, E and F:
These clearances may be reduced to 25mm without
affecting the performance of the boiler. In order to
ensure that the condensate plume does not affect
adjacent surfaces the terminal should be extended as
shown in ¬fig.7.6.
2) Dimension H:
This clearance may be reduced to 25mm without
affecting the performance of the boiler. However, in
order to ensure that the condensate plume does not
affect adjacent surfaces a clearance of 300mm is pre-
ferred. For IE, recommendations are given in the cur-
rent edition of IS813.
For 1 and 2 above you can use the Variable Termination Kit
to move the termination point away from the building fab-
ric.
Article numbers:
0020060584 - White
0020060585 - Black
7.6 Termination of air/flue gas duct under balcony or eaves

Table of Contents

Other manuals for Vaillant ecoTEC plus SERIES

Related product manuals