EasyManuals Logo

Vaillant ecoTEC plus SERIES Installation And Maintenance Instructions

Vaillant ecoTEC plus SERIES
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Start-up
46 Installation and maintenance instructions ecoTEC plus 0020116700_01
10
1
2
10.7 Measuring the gas inlet working pressure
> Undo the sealing screw of the measuring nipple (1)
(lower screw) at the gas valve using a screwdriver.
> Connect a digital pressure gauge or U-tube manometer
(2) to the measuring nipple (1).
> Open the gas isolation valve of the boiler.
> Start the boiler by activating the test program P.01 as
described in ¬section13.4.
> In addition, ensure that maximum heat can be dissipated
into the heating system by turning up the room thermo-
stat.
> Alternatively, for VUW-boilers: fully open the hot water
taps to ensure full flow rate through the boiler.
> With the boiler operating at full load check that the gas
inlet working pressure at the reference test point (1)
complies with the requirements of ¬table 10.3.
> Should the pressure recorded at the reference test point
in the boiler be lower than indicated (¬table 10.3) check
if there is any blockage in the pipework or if the pipe-
work is undersized.
If the supply pressure is out of tolerance contact your
Emergency Service Provider.
If the gas inlet working pressure at the reference test point
(1) is not within the permissible range and you cannot cor-
rect the failure, notify the gas supply company or the Vail-
lant Service Solutions (0870 6060 777) and proceed as fol-
lows:
> Take the boiler out of operation by
terminating test program P.01 as described in
¬section10.4.
Only for VUW-boilers: Allow the boiler to cool down by
turning off water taps and allow pump overrun to
operate for a minimum of two minutes.
> Close the gas isolation valve of the boiler.
> Remove the pressure gauge and retighten the sealing
screw (1) for the measuring nipple.
> Turn on gas at the gas isolation valve.
> Make sure that there is no leakage at the sealing screw.
> Turn off gas at the gas isolation valve.
> Put the front casing back on.
> Turn off electrical supply to the boiler.
> You must not start up the boiler.
If the gas inlet working pressure is within the permissible
range, proceed as follows:
> T
ake the boiler out of operation by
terminating test program P.01 as described in
¬section10.4.
Only for VUW-boilers: Allow the boiler to cool down by
turning off water taps and allow pump overrun to
operate for a minimum of two minutes.
> Close the gas isolation valve of the boiler.
> Remove the pressure gauge and retighten the sealing
screw (1) for the measuring nipple.
> Open the gas isolation valve of the boiler.
> Make sure that there is no leakage at the sealing screw.
> Put the front casing back on.
> Reset boiler controls for normal operation.
> Record the boiler gas inlet working pressure (kPa
resp.mbar) in the Benchmark gas boiler commissioning
checklist.
Boiler
Natural gas (G20) LPG (G31)
Minimum
pressure at
reference
test point in
kPa (mbar)
Maximum
pressure at
reference
test point in
kPa (mbar)
Minimum
pressure at
reference
test point in
kPa (mbar)
Maximum
pressure at
reference
test point in
kPa (mbar)
612/
615/
618/
624/
630/
824/
831
1,6 (16) 2,3 (23) 2,3 (23) 4,3 (43)
637/
837
1,5 (15) 2,3 (23) 2,3 (23) 4,3 (43)
10.3 Gas inlet working pressure at the reference test point
10.12 Carrying out a full function test
> After completing the installation and the gas setting, per-
form a complete function check of the boiler before start-
ing up the boiler and handing it over to the operator.

Table of Contents

Other manuals for Vaillant ecoTEC plus SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ecoTEC plus SERIES and is the answer not in the manual?

Vaillant ecoTEC plus SERIES Specifications

General IconGeneral
ModelecoTEC plus SERIES
MountingWall-mounted
Fuel TypeNatural Gas / LPG
ErP Heating Efficiency ClassA
NOx Class5
CategoryBoiler
TypeCondensing
EfficiencyUp to 94%
ErP Water Heating Efficiency ClassA

Related product manuals