USER'S GUIDE____________________________________________________________________
50 __________________________________________________________________ M211372EN-B
Select Unit
Use the UNIT command to select metric or non-metric output units.
UNIT [x]<cr>
where
x = Selects the unit type to output:
m = metric units, for example, Celsius
n = nonmetric units, for example, Fahrenheit
Example:
unit m
Units : Metric
Configuring Serial Line Operation
Set Serial Line Operating Mode
Use the SMODE command to set the start-up operating mode of the
serial line.
SMODE [mode]<cr>
where
mode = STOP, RUN, or POLL.
Table 9 Selection of Output Modes
Mode Measurement Output Available Commands
STOP Only with the SEND command. All (default mode).
RUN Automatic output. Only command S.
POLL Only with the SEND [addr]
command.
SEND [addr] and OPEN [addr].
Other commands available after
opening a line to the transmitter
using the OPEN command.
Use with RS-485 buses where
multiple transmitters can share
the same line.
Selected output mode will be activated at next reset or power up.
Example:
smode poll
Serial mode : POLL