User's Guide _______________________________________________________________________ 
20  ___________________________________________________________________ M211659EN-C 
DIP Switches of Analog Output Models 
 
1402-027   
Figure 6  DIP Switch Settings of Analog Output Models 
Td (dewpoint) as humidity parameter on display and 
analog output. Sets analog output scaling 
RH (relative humidity) as humidity parameter on display 
and analog output. Sets analog output scaling to 
Set analog output channels to 0 ... 5 V (voltage output) or 
0 ... 20 mA (current output) 
Set analog output channels to 0 ... 10 V (voltage output) 
or 4 ... 20 mA (current output) 
Configuration through service port only. 
Configuration by DIP switches only. 
Resets display analog outputs to standard settings. 
 
NOTE 
If DIP switch 8 is set to Custom, the transmitter ignores all other DIP 
switch settings. In custom mode the transmitter uses settings that are 
configured in software using the service port. Before changing the 
position of this switch, see section Changing Between DIP and Custom 
Configuration on page 21. 
 
Non-Metric
Td
0...20mA
Custom
Metric
RH
4..20mA
DIP
1
2
3 4
5 6
7
8
Non-Metric
Td
Custom
Metric
RH
DIP
1
2 3 4
5 6
7
8
GMW93 GMW94
0...5V
0...10V