Appendix A _________________________________________________________ BACnet Reference
VAISALA ________________________________________________________________________ 89
Carbon Dioxide Object
Table 20 Carbon Dioxide Object Properties
Property
Data type
(Application Type)
Writable
(Conformance Code)
Value or Initial Value
Persistence
Object_Identifier
BACnetObjectIdentifier
No (R)
00 00 00 01 (hex)
Object Type = 0,
Instance = 1
Nonvolatile
Object_Name
CharacterString
No (R)
"CO2"
Nonvolatile
Object_Type
BACnetObjectType
(ENUMERATED)
No (R)
0 (Analog Input)
Fixed
Present_Value
Real
Yes
(When Oos) (R)
0.0
Volatile
Description
CharacterString
No (O)
"Carbon Dioxide"
Nonvolatile
Units
BACnetEngineeringUnits
(ENUMERATED)
No (R)
96 (parts-per-million)
Nonvolatile
Status_Flags
BACnet Status Flags
(BIT STRING)
Yes (when OoS) (R)
0 (FAULT == FALSE)
Volatile
Reliability
BACnet Reliability
(ENUMERATED)
Yes (when OoS) (O)
0 (NO FAULT
DETECTED)
Volatile
Event State
BACnetEventState
(ENUMERATED)
No (R)
0 (NORMAL)
Volatile
Out_of_Service
BOOLEAN
Yes (R)
0 (FALSE)
Volatile
COV_Increment
Real
Yes (O)
NaN (COV reporting
disabled)
Nonvolatile
Min_Pres_Value
Real
No (O)
0.0 (same as limit for
UNDER_RANGE)
Nonvolatile
Max_Pres_Value
Real
No (O)
2400 (same as limit for
OVER_RANGE)
Nonvolatile
Table 21 Status Flags
Flag
State
Cause
IN_ALARM
FALSE
Event State equals 0 (NORMAL)
TRUE
Event State not 0
FAULT
FALSE
Reliability equals 0 (NO FAULT DETECTED)
TRUE
Reliability not 0
OVERRIDDEN
FALSE
Always FALSE
OUT_OF_SERVICE
FALSE
Present Value may NOT be written via BACnet
TRUE
Present Value may be written via BACnet
1)
Table 22 Reliability
State
Cause
0 NO_FAULT_DETECTED
1 NO_SENSOR
No contact to measurement module
2 OVER_RANGE
CO2 level over BAC_CO2_MAX_VALUE
3 UNDER_RANGE
CO2 level under BAC_CO2_MIN_VALUE
7 UNRELIABLE_OTHER
Other measurement error
Table 23 Event State
State
Cause
0 NORMAL
Reliability equals 0 (NO FAULT DETECTED)
1 FAULT
Reliability not 0

Table of Contents

Other manuals for Vaisala GMW95

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaisala GMW95 and is the answer not in the manual?

Vaisala GMW95 Specifications

General IconGeneral
BrandVaisala
ModelGMW95
CategoryTransmitter
LanguageEnglish

Related product manuals