Object_Identifier: Must be unique in BACnet network. As Object 
Identifier is 22 bits long its value range is 0 ... 4194303. Each device is 
assigned a random value in this range at Vaisala factory. 
Object_Name: Must be unique in BACnet network. Default object name 
contains the name and serial number of the device. For example, 
transmitter model GMW95 with serial number G1234567 receives the 
default object name "GMW95_G1234567". 
System_Status: System status can be OPERATIONAL (0) or 
NON-OPERATIONAL (4). Device goes to NON-OPERATIONAL state 
in case of fatal error. 
Protocol_Services: Who-Is, I-Am, Who-Has, I-Have and 
UnconfirmedCOVNotification services are available only when XMW90 
is MS/TP master. Reinitialize Device service must be password 
protected. According to BACnet protocol, password is character string 
having max 20 characters. Default password is "1234". Password can be 
changed through the service port by using the BACNET command. See 
section Set BACnet Parameters on page 61. 
Database_revision: This is changed during operation according to 
section 12.11.35 of ANSI/ASHRAE standard 135-2008.