User's Guide _______________________________________________________________________
46 ___________________________________________________________________ M211659EN-C
Now give the following AOVER command:
>aover 3 5 10
Aout 3 clipping : 5.00 %
Aout 3 error limit : 10.00 %
Channel 3 now behaves like this:
- Clipping is now set to 5%, meaning the output is allowed to vary
between 0 ... 5.25 V. The channel will output the measurement for
0 ... 2100 ppm, but range 0 ... 5 V remains scaled to 0 ... 2000 ppm.
- Error limit is 10%, which means channel 3 will show the error state
(5.5 V) when the measured value is 10% outside the scaled output
range. With the settings above, this will happen if the measured
temperature is outside range 0 ... 2100 ppm.
- The output will never actually be between 5.25 and 5.5 V because of
clipping.