Figure 15 Inside Power Supply Unit cabinet
(OPTPSU1 and OPTPSU2)
1 Circuit breaker for AC or DC power
(F1)
2 Surge arresters
3 Power switch (S1)
4 Power supply
5 Relays (3 pcs). Each relay has a LED
that is lit when the relay is active.
6 DC OK LED. If flashing, check DC
output wiring.
7 DC out terminal block (X5)
8 Relay control terminal block (X4)
9 Relay output terminal block (X3)
10 Mains power in terminal block (X1)
4.4 Grounding DGA monitor
Grounding cable with 4 … 16mm
2
(12 … 5 AWG) conductor. Enough to reach
from the DGA monitor and the power supply unit to the grounding point(s).
Cable stripping tool
Crosshead screwdriver
Metal file
Multimeter
1. Locate the ground terminals on the underside of the DGA monitor and the power supply
unit, and find a good grounding point on the transformer or the surrounding structures.
2. Clean the grounding point of rust for a good connection.
OPT100 Installation Guide M211857EN-R