3. To set up time synchronization with a Network Time Protocol (NTP) server:
NTP synchronization requires that the network connection is configured and
the IP address of the NTP server is reachable.
a. Select Use NTP.
b. Enter the IP address of the NTP server into NTP server.
c. Select Apply to start time synchronization.
Status of time synchronization is shown below the NTP server field. If the status
shows Connecting... and does not progress to Synchronizing time... even after
waiting for a minute, verify that the network connection is working and configured,
and the IP address of the NTP server is correctly entered.
d. Wait for the message Time successfully synchronized to appear.
4. To set up time synchronization using DNP3 protocol:
a. Enable and configure the DN3 protocol.
b. Select Use DNP3.
c. Select Apply to start time synchronization.
More information
‣
Configuring DNP3 protocol (page 77)
5.8
Initializing DGA monitor
• 5-mm Allen key
Before starting the initialization, make sure that:
• DGA monitor is fully installed and wired.
• All oil connections are completed.
• DGA monitor is turned on.
• You are connected to the user interface with a web browser.
You must have physical access to the DGA monitor cabinet and the oil valves on
the transformer. Do not try to perform the initialization remotely.
You can stop the initialization sequence at most phases by selecting Control >
Cancel.
OPT100 Installation Guide M211857EN-R
72