3. Select Start to enable the protocol test mode and open the protocol test mode page.
The page is preconfigured with arbitrary default values for measurement
parameters. The values are all dierent to make it easy to verify on the
SCADA side that the correct parameter is being read and displayed. Scroll
the page to reveal all of the fields.
4. To set your own test data:
a. Edit the values as required.
b. Check the checkboxes to enable the desired caution and warning level alerts.
c. Select Update at the bottom of the page to take the new test data into use.
5. The test mode will end automatically after one hour. You can select a longer timeout from
the drop-down menu marked Test mode timeout in. Select Update to take the new
timeout into use.
6. Start testing by reading information from the DGA monitor from the SCADA system side.
7. When you are done testing, select Close to end the test mode immediately or wait until
the end of the timeout.
5.14
Configuring gas level alerts
Figure 39 Alert limits settings page
OPT100 Installation Guide M211857EN-R
80