While waiting between the initialization steps, you can navigate away from the
Control page and access the other pages (for example, to perform system
configuration tasks). Remember to come back to the Control page to complete
the initialization.
1. In the user interface, select Control.
2. Read the instructions on screen and verify that DGA monitor is waiting to be initialized.
3. Select Start to start the initialization sequence.
4. Turn the gray knob on the side of the bleed valve 90° counterclockwise to open the
manual override lock. The knob pops outward when the lock is open. Select OK when
done.
The initialization sequence performs a test to verify that the manual lock on
the bleed valve is now open. In rare cases, it is possible for the test to fail
even if the lock has been opened. If the test fails, you can choose to skip the
test and proceed with the initialization. Skip the test only if you are certain
the lock is open.
Chapter 5 – Commissioning
73