CAP. 16 - MESSAGE AND ALARM CODES 66 / 74 ENGLISH
ClimFill Maxi
CODE MESSAGE When it occurs Possible
situations
Actions
W036 FURTHER OIL
INJECTION NOT
POSSIBLE
During oil
injection phase
Insufficient
vacuum level
Increase the vacuum
phase time, check the
A/C system tightness.
W044 VESSEL EMPTY During flushing
or Tank
refrigerant
internal re
cycling phase
Gas level is
too low for the
procedure to
be completed
Fill the internal tank
with gas
W045 LP VERY LOW,
CHECK CIRCUIT
BEFORE
CONTINUING
During flushing
phase
LP hose
disconnected,
flushing
couplings not
properly
connected or
leak in circuit
being flushed.
Reconnect LP and/or
the fittings and
eliminate any leaks.
W047 POSSIBLE
LEAKAGE
During the
refrigerant
recovery phase
Vehicle A/C
system may
have leaks
--