Technical description 6 Communication 6.2 Communication protocols
VM50.EN004 VAMP 24h support phone +358 (0)20 753 3264
181
6.2.8. Ethernet port
IEC61850 and Modbus TCP uses Ethernet communication.
Also VAMPSET, SPA-bus and DNP 3.0 communication can be
directed via TCP/IP.
Parameters
Parameter Value Unit Description Set
Protoc None
SpaBus
ModBusTCPs
DNP3
IEC-61850
Ethernet port protocol
Set
Port nnn
Ip port for protocol,
default 102
Set
IpAddr n.n.n.n
Internet protocol
address (set with
VAMPSET)
Set
NetMsk n.n.n.n
Net mask (set with
VAMPSET)
Set
Gatew default = 0.0.0.0
Gateway IP address (set
with VAMPSET)
Set
NTPSvr n.n.n.n
Network time protocol
server (set with
VAMPSET)
0.0.0.0 = no SNTP
Set
VS Port nn IP port for Vampset Set
KeepAlive nn TCP keepalive interval Set
MAC nnnnnnnnnnnn MAC address
Msg# nnn Message counter
Errors nnn Error counter
Tout nnn Timeout counter
Set = An editable parameter (password needed)
6.2.9. External I/O (Modbus RTU master)
External Modbus I/O devices can be connected to the relay
using this protocol. (See chapter 8.7.1 External input / output
module for more information).
6.2.10. IEC 61850
IEC 61850 protocol is available with the optional
communication module. IEC 61850 protocol can be used to read
/ write static data from the relay to receive events and to
receive / send GOOSE messages to other relays.
IEC 61850 serve interface is capable of.