EasyManuals Logo

VAMP 50 User Manual

VAMP 50
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
6.1 Communication ports 6 Communication Technical description
170
VAMP 24h support phone +358 (0)20 753 3264 VM50.EN004
6.1.2. Remote port
Parameters
Parameter Value Unit Description Note
Protocol
None
SPA-bus
ProfibusDP
ModbusSla
ModbusTCPs
IEC-103
ExternalIO
DNP3
Protocol selection for
remote port
-
SPA-bus (slave)
Profibus DB (slave)
Modbus RTU slave
Modbus TCP slave
IEC-60870-5-103 (slave)
Modbus RTU master for
external I/O-modules
DNP 3.0
Set
Msg#
0 ... 2
32
1
Message counter since the
device has restarted or
since last clearing
Clr
Errors
0 ... 2
16
1
Protocol errors since the
device has restarted or
since last clearing
Clr
Tout
0 ... 2
16
1
Timeout errors since the
device has restarted or
since last clearing
Clr
speed/DPS
Display of current
communication
parameters.
speed = bit/s
D = number of data bits
P = parity: none, even,
odd
S = number of stop bits
1)
Debug
No
Binary
ASCII
Echo to local port
No echo
For binary protocols
For SPA-bus protocol
Set
Set = An editable parameter (password needed)
Clr = Clearing to zero is possible
1) The communication parameters are set in the protocol specific menus. For
the local port command line interface the parameters are set in
configuration menu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the VAMP 50 and is the answer not in the manual?

VAMP 50 Specifications

General IconGeneral
BrandVAMP
Model50
CategoryRelays
LanguageEnglish

Related product manuals