5.8 Auto-reclose function (79)
5 Control functions
Technical description
154
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
Parameter
Value
Unit
Default
Description
Shot settings
DeadT
0.02 … 300.00
s
5.00
The dead time setting for this
shot. This is a common setting
for all the AR lines in this shot
AR1
On; Off
-
Off
Indicates if this AR signal
starts this shot
AR2
On; Off
-
Off
Indicates if this AR signal
starts this shot
Start1
0.02 … 300.00
s
0.02
AR1 Start delay setting for this
shot
Start2
0.02 … 300.00
s
0.02
AR2 Start delay setting for this
shot
Discr1
0.02 … 300.00
s
0.02
AR1 Discrimination time
setting for this shot
Discr2
0.02 … 300.00
s
0.02
AR2 Discrimination time
setting for this shot