Series 612 INSTALLATION
605262EE Edition 2018-08-20 67/
4.9.2.2 Details
Signal
Type
Name
Byte
Length
Data
Type
Valid
Range
Description
Signal
PRESSURE
4
signed
integer
(default) or
floating point
-270000..
1’230’000
(default)
(-2.7V..12.3V
sensor signal),
adjustable
1)
In case of default valid range:
Physical full scale value of the sensor (10
Volt) equals to 1’000’000.
(In case of 2 sensor operation the full scale
of high range sensor equals to 1’000’000.)
Signal
PRESSURE SENSOR 1
4
signed
integer
(default) or
floating point
-270000..
1’230’000
(default)
(-2.7V..12.3V
sensor signal),
adjustable
1)
In case of default valid range:
Physical full scale value of the sensor (10
Volt) equals to 1’000’000.
Signal
PRESSURE SENSOR 2
4
signed
integer
(default) or
floating point
-270000..
1’230’000
(default)
(-2.7V..12.3V
sensor signal),
adjustable
1)
Optional, only in case of 2 sensor version.
In case of default valid range:
Physical full scale value of the sensor (10
Volt) equals to 1’000’000.
Signal
POSITION
4
signed
integer
(default) or
floating point
0..100’000
(default),
adjustable
1)
min signal value = “valve is closed”
max signal value = “valve is opened”
The position 9’999’999 (or 9’999’999.0 for
floating point) show an unknown valve
position – e.g. during synchronization at
startup
If Isolation valve failure is active(only Series
951 / 952):
The position = ((max signal value - min
signal value) * 0.2) + min signal value.
e.g.: max signal value = 100’000
min signal value = 0
Position = ((100’000 – 0) * 0.2) + 0 =
20’000
Signal
CONTROL MODE
1
unsigned
integer
0…14
0 = init
1 = synch
2 = position
3 = close
4 = open
5 = pressure
6 = hold
7 = learn
8 = interlock open
9 = interlock close
10 = maintenance open
11 = maintenance close
12 = power failure
13 = safety
14 = fatal error