60
Operations Alarms
Table 6 summarizes Hose Setup warning messges and Table 7 contains wireless related alarms.
afnn: CHK VAPOR FLOW MTR Red Failure of locked rotor test - possible
locked Air Flow Meter.
Locked rotor test passes or Air
Flow Meter deconfigured, or test
cleared.
Table 6. Hose Setup Data Warning Messages
Message Cause Action
Label Not Assigned Missing hose label selection
Check hose settings in Setup>Vapor
Collection>Hose Settings
FP Label Not Set Fuel Position label not set.
Air Flow Meter Not Assigned
Air Flow Meter not selected and
assigned to the hose.
Assigned Air Flow Meter Not
Configured
Air flow meter is assigned to a
hose but is disabled in Device
Setup.
Check Air Flow Meter setup in
Setup>Device>Air Flow Meter
Meter Not Mapped Fuel meter not mapped to hose.
Check meter mapping in Setup>Vapor
Collection>Hose Mapping
Table 7. Wireless Related Sensor Alarms
Displayed Message Devices
Light
Indicator Description
Suggested
Troubleshooting
BATTERY WARNING Vapor Valve, VPS,
AFM and Probe
Yellow Device transmitter reports
battery status as
‘Replace’ for 24 hours
Remove and
replace battery
pack
Table 5: Other Alarms
Displayed Message
Light
Indicator Set Condition Clear Condition

Table of Contents

Other manuals for Veeder-Root TLS-450PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-450PLUS and is the answer not in the manual?

Veeder-Root TLS-450PLUS Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-450PLUS
CategoryMusic Mixer
LanguageEnglish

Related product manuals