78
Operations Viewing ISD Reports via RS-232 Connection
Figure 107 shows an example V-R Vapor Polisher Runtime Diagnostic Report and Table 10 explains the IV8000
report’s
event codes (not available with FFS-CAS or Hirt VCS 100).
Figure 107. Vapor Polisher Runtime Diagnostics Report - Serial to PC Format
Table 10: Vapor Processor Runtime Diagnostic Report Event Codes
Event Code Cause Event Code Cause
NO EVENT The valve changed state outside of the car-
bon canister algorithm.
CLOSE NEAR
FULL
Canister load is between 80 and 100% and pressure
is <1.05.
CLOSE TEST Manual operation of the valve OPEN PURGE Canister load is >0% and pressure <-0.25
OPEN TEST Manual operation of the valve OPEN EXCESS
PURGE
Canister load is 0%, Excess purge is incomplete,
pressure <-1.5, time is between 6AM and 4PM.
CLOSE
PURGE HI P
The canister state is in excess purge and the
pressure is above -0.5.
OPEN FILL Canister valve is open for loading:
When pressure is greater than or equal to 0.75
IWC and Canister load is less than 80%.
Pressure is greater than or equal to 1.3 IWC and
Canister load is greater than 80%.
CLOSE
PURGE TIME
The canister state is in excess purge and the
time is outside 6AM to 4PM.
CLOSE CVLD
TEST
Valve was closed to collect data for ISD contamina-
tion leak test.
CLOSE
FORCE
PURGE
Canister is in startup period. Loading with
pressures <+1.05 is not allowed until startup
period is complete.
CLOSE LIMIT Valve closed because canister has reached allowable
extended capacity loading limit.
CANISTER
EMPTY
Canister was loaded above 1% and purged
to 0%. No valve state change.
CANISTER FULL No valve state change. The canister load passed from
below 95% to/thru the 100% point and not yet at
day’s emission limit.
CLOSE EMPTY Excess purging has completed.
IV8000
FEB 4, 2008 1:01 PM
TLS_350 UST
VEEDER-ROOT TEST LAB
125 POWDER FOREST DR
SIMSBURY, CT 06070
VAPOR POLISHER
VALVE EVENT PRESSURE
DATE-TIME "WC EVENT CODE
1-31-08 3:44PM -0.700 OPEN PURGE
1-31-08 3:47PM 0.038 CLOSE FORCE PURGE
1-31-08 3:51PM -0.255 OPEN PURGE
1-31-08 8:08PM -0.300 CLOSE PURGE Hi P
2-01-08 1:59PM -0.300 OPEN PURGE
2-01-08 2:18PM -0.263 OPEN PURGE
2-01-08 2:33PM -0.289 OPEN PURGE
2-04-08 11:22AM -0.560 NO EVENT
2-04-08 11:28AM -0.560 OPEN PURGE
2-04-08 11:48AM -0.300 OPEN PURGE
2-04-08 12:28PM -0.263 OPEN PURGE
2-04-08 12:42PM -0.299 OPEN PURGE