9 Diagnosis, asset management and service
VEGAPULS 69 • Foundation Fieldbus
47251-EN-160815
Code
Text message
Cause Rectication DevSpec
Diagnosis Bits
F125
Impermissible electronics
temperature
– Temperature of the
electronics in the non-
speciedrange
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
Bit 7
F260
Error in the calibration
– Error in the calibration
carried out in the factory
– Error in the EEPROM
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 8
F261
Errorintheconguration
– Error during setup
– False signal suppression
faulty
– Error when carrying out
a reset
– Repeat setup
– Repeat reset
Bit 9
F264
Installation/Setup error
– Adjustment not within
the vessel height/meas-
uring range
– Max. measuring range
of the instrument not
sucient
– Check or correct instal-
lation and/or parameter
adjustment
– Use an instrument with
bigger measuring range
Bit 10
F265
Measurement function dis-
turbed
– Sensor no longer carries
out a measurement
– Operating voltage too
low
– Check operating voltage
– Carry out a reset
– Disconnect operating
voltagebriey
Bit 11
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Text message
Cause Rectication DevSpec Diagnosis Bits
C700
Simulation active
– A simulation is active – Finish simulation
– Wait for the automatic
end after 60 mins.
Bit 27
The following table shows the error codes and text messages in the
status message "Outofspecication" and provides information on
causes as well as corrective measures.
Code
Text message
Cause Rectication DevSpec State Diagno-
sis Bits
S600
Impermissible electronics
temperature
– Temperature of the
electronics in the non-
speciedrange
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
Bit 23
Function check
Outofspecication