EasyManua.ls Logo

Verderflex Ds500+ - Calibration and Pump Settings

Default Icon
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19 | Page
Version 00
© Verder Liquids B.V
Ds500, Ds500+ Operating manual
Original instructions (en)
10.3 Main Menu
From this screen the operator can access other sub-menus:
Figure 13. - Main menu
Symbol Description
MODE
Operational mode
Pump settings
Cartridge information
Fluid level monitor
Security settings
Pump information
Press to return to the home screen at any time
I/O settings (Ds500+ model only)
Go to previous screen
Table 14. - Main menu symbols
MODE
10.3.1 Operational mode
Figure 14. - Operational mode
Available control modes:
Manual (default mode)
4-20mA (Ds500+ only)
Contact (Ds500+ only)
Note: The pump will not start when in 4-20mA or contact mode
if there is a pump head issue. This is to prevent unintentional
operation when remotely controlled. Manual operation is still
possiblewithaconrmationdialogue.
Flow calibration Fluid recovery
Change control
mode
10.3.1.1 4-20mA Calibration
Externalcontrolsignalscanbeusedtocontroltheowofthe
unit. To do so, calibration must be performed:
Figure 15. - 4-20mA Calibration (1)
The above screen is awaiting a 20mA input signal (±1mA).
Once20mAisreached,conrmationisrequired:
Figure 16. - 4-20mA Calibration (2)
At this point, 20mA can be set to to suit the application,
e.g., 20mA = 65 rpm:
Figure 17. - 4-20mA Calibration (3)
The same procedure needs applying to the 4mA input signal:
Figure 18. - 4-20mA Calibration (4)
At this point, 4mA can be set to to suit the application,
e.g., 4mA = 0 rpm.
Once calibration is complete, the speed can be set proportionally
bytheexternalcontrolsignal.

Table of Contents

Related product manuals