Liebert CR012 Precision Air Conditioning User Manual
3.7.5 Parameter setting
Table 3-6 Teamwork parameters
Menu
Parameter
Default
Range
Teamwork Set
Mode
SINGLE
SINGLE/TEAM
Unit Addr
0
0~15
Units Qty
1
1~16
Stdby Qty
0
0~15
Rotate Qty
0
0~8
Rot Freq
NONE
NONE/DAILY/MON/TUE/WED/THU/FRI/SAT/SUN
Rotate At
12:00
00
00~23
00
M/S Dly
2 min
0~10min
Manu Rotate
NO
NO/YES
Unit with teamwork address 0 is defined as the master unit. Units with the non-zero address are defined as the slave
units. Teamwork parameters only can be set in master unit and shared to the slave units. Slave units can only
configure their own teamwork address.
Select Teamwork Setting from the System Setting, the following menus appear:
Unit Addr 0
Units Qty 1
Stdby Qty 0
Mode SINGLE
Rot Freq NONE
Rotate Qty 0
Rotate At 1200
M/S Dly 2min
Manu Rotate YES
Figure 3-41 Teamwork control menu
Mode: Selections are SINGLE or TEAM.
Unit Addr: Range is 0~15. Master unit is 0; others are 1, 2, 3..., etc. Teamwork address must be consecutive.
Example: There are 8 units in teamwork, thus teamwork address must be 0, 1, 2, 3, 4, 5, 6, 7.
Units Qty: Range is 1~16. Example: There are 8 units in teamwork, thus set as 8.
Stdby Qty: Range is 0~ (Unit Qty-1). Example: There are 8 units in teamwork, thus standby quantity can be any of
from 0 to 7.
Rotate Qty: Defines a number of units rotate at each rotation. This parameter is effective only when Rotation Freq is
other than None and Rotation Qty is non-zero. Example: Unit Qty is 8.
Standby Qty is 1. Rotation Qty is 1. Operation units are 0 to 6. At the time of rotation, operation unit changes to 1 to 7.
Rot Freq: Defines for how many days (or which day) rotation occurs. Select None to disable rotation function.
Rotate At: The time when rotation occurs.
M/S Dly: When performing a rotation, after the standby unit has turned on, the operating unit has to wait 2 minutes
(default) before turning off.
Manu Rotate: During teamwork debugging, each manual rotation will execute a regular rotation with rotation quantity.