Unit with teamwork address 0 is defined as the master unit. Units with the non-zero address are defined as the slave
units. Teamwork parameters only can be set in master unit and shared to the slave units. Slave units can only
configure their own teamwork address.
Select Teamwork Setting from the System Setting, the following menus appear:
Figure 3-41 Teamwork control menu
Mode: Selections are SINGLE or TEAM.
Unit Addr: Range is 0~15. Master unit is 0; others are 1, 2, 3..., etc. Teamwork address must be consecutive.
Example: There are 8 units in teamwork, thus teamwork address must be 0, 1, 2, 3, 4, 5, 6, 7.
Units Qty: Range is 1~16. Example: There are 8 units in teamwork, thus set as 8.
Stdby Qty: Range is 0~ (Unit Qty-1). Example: There are 8 units in teamwork, thus standby quantity can be any of
from 0 to 7.
Rotate Qty: Defines a number of units rotate at each rotation. This parameter is effective only when Rotation Freq is
other than None and Rotation Qty is non-zero. Example: Unit Qty is 8.
Standby Qty is 1. Rotation Qty is 1. Operation units are 0 to 6. At the time of rotation, operation unit changes to 1 to 7.
Rot Freq: Defines for how many days (or which day) rotation occurs. Select None to disable rotation function.
Rotate At: The time when rotation occurs.
M/S Dly: When performing a rotation, after the standby unit has turned on, the operating unit has to wait 2 minutes
(default) before turning off.
Manu Rotate: During teamwork debugging, each manual rotation will execute a regular rotation with rotation quantity.