3.5.3 Humidification Control
To prevent the humidifier from running when not required (especially when return air temperatures
exceed 75°F [24°C]), the default control for humidity and dehumidification is based on dew point
temperature, not relative humidity. If this default control is changed, adjust the relative humidity setpoint
based on return air temperature to prevent from over-humidifying the space.
3.6 Shipping Dimensions and Unit Weights
Model #
Domestic Packaging Export Packaging
Dry Weight, lb
(kg)
Unit
Ship Weight, lb
(kg)
Shipping Dimensions, in.
(mm)
Ship Weight, lb
(kg)
Shipping Dimensions, in.
(mm)
DA050*A
DA050*P
2012 (913)
97 X45 X 82
(2464 X 1143 X 2083)
2182 (990)
97 X 45 X 82
(2464 X 1143 X 2083)
1590( 721)
DA080*A
DA080*P
2250 (1021)
120 X 45 X 85
(3048 X1143 X2159)
2450(1111)
120 X 45 X85.5
(3048 X 1143 X2172)
2200 (998)
DA085*A
DA085*P
2350 (1066)
120 X 45 X 85
(3048 X 1143 X 2159)
2550 (1157)
120 X 45 X85.5
(3048 X 1143 X2172)
2250 (1021)
DA125*A
DA125*P
3450 (1565)
153 X 54 X 85
(3886 X 1372 X 2159)
3650 (1656)
153.5 X 54.5 X 85.5
(3899 X 1384 X 2172)
3465 (1572)
DA150*A
DA150*P
3570 (1619)
153 X 54 X 85
(3886 X 1372 X 2159)
3770 (1710)
153.5 X 54.5 X 85.5
(3899 X 1384 X 2172)
3574 (1621)
DA165*A
DA165*P
3754 (1703)
153 X 54 X 85
(3886 X 1372 X 2159)
3954 (1794)
153.5 X 54.5 X 83.5
(3899 X 1384 X 2121)
3574 (1621)
Table 3.3 Downflow unit domestic and export shipping dimensions and weights
Model #
Domestic Packaging Export Packaging
Dry Weight, lb
(kg)
Unit Ship Weight, lb
(kg)
Shipping dimensions, in.
(mm)
Ship Weight, lb
(kg)
Shipping dimensions, in.
(mm)
DA080U*A
DA080U*P
2270 (1030)
120 X 45 X 85
(3048 X 1143 X 2159)
2470 (1120)
120 X 45 X85.5
(3048 X 1143 X 2172)
2150 (975)
DA085U*A
DA085U*P
2370 (1075)
120 X 45 X 85
(3048 X 1143 X 2159)
2570 (1166)
120 X 45 X85.5
(3048 X 1143 X 2172)
2150 (975)
Table 3.4 Upflow unit domestic and export shipping dimensions and weights
Vertiv | Liebert® DSE™ Installer/User Guide
22