5.1.2 Condensate-pump Drain Line Requirements
NOTICE
Risk of water backing up in the drain line. Leaking and overflowing water can cause equipment
and building damage.
Do not install an external trap in the drain line. This line already has a factory-installed trap
inside the cabinet. Installation of a second trap will prevent drain-water flow and will cause the
water to overflow the drain pan.
This line may contain boiling water. Use copper or other material that is rated for handling
boiling water for the drain line. Sagging condensate drain lines may inadvertently create an
external trap.
Observe the following requirements when installing and routing the drain line:
• The drain line must be located so it will not be exposed to freezing temperatures.
• Size the piping based on the available condensate head.
• Drain is trapped internally. Do not externally-trap the drain line.
• The drain line must be rigid enough that it does not sag between supports, which
unintentionally creates traps.
• Use copper or other material suitable for draining water that can reach temperatures up to
212°F (100°C).
• We recommend installing monitored, under-floor leak-detection equipment.
Factory-installed Condensate Pump
If your unit includes an optional condensate pump, the pump is factory-installed inside the unit and a
1/2-in. copper sweat connection is provided on the unit.
• On 60-Hz units, the condensate pump is rated for approximately 400gphat 10ft
(1514l/mat3m) total head.
• On 50-Hz units, the condensate pump is rated for approximately 315gphat 10ft (1192l/m at
3m) total head.
5.1.3 Water Supply-line Requirements for the Optional Humidifier
The unit may have an optional humidifier. Refer to the appropriate supply-line piping requirements if a
humidifier is included on your unit:
Infrared Humidifier:
• 1/4-in. supply line, maximum water pressure is 150 psi (1034kPa).
• Size supply line for 1 gpm (3.8 l/m), with a minimum water pressure of 20psi(138kPa).
• Do not supply de-ionized water to the humidifier.
Vertiv | Liebert® DSE™ Installer/User Guide
34