Vertiv | Liebert® EDGE | Installer/User Guide
23
Dischg protect time
Sets the maximum discharge time for the UPS. The default setting is the maximum allowing the
battery to fully discharge. This can be set lower to limit the amount of time the UPS will provide battery
protection after which it will shut down. If the discharge time remaining on the battery is lower than the
setting value, it will have no eect.
• 1 - 4320 minutes (default of 4320)
Max chg curr
Sets the maximum charge current for the battery. A higher charge current will charge the battery more
quickly but can shorten battery life. A lower value will lengthen the battery charge time and can increase
battery life. The load is always prioritized and the charge current will be decreased internally if necessary
to support the load.
• 1/2/3 A (default of 1) only for 2U/3U model.
Temp compensation
When enabled, the UPS will adjust the charging voltage of the batteries based on temperature in order
to preserve battery life. It will increase the voltage if the UPS is operating in a cold environment. It will
decrease the voltage if the UPS is operating in a warm environment.
• Enable
• Disable (default)
Replace battery
Activates newly-installed battery packs after replacement and reset all battery statistics for new battery
Packs.
• Provides a conrmation window with Yes/No options to conrm replacement of batteries.
Monitor Settings Options
Language
Selects the language of the display options are:
• English (default)
• French
• Portuguese
• Spanish
• Chinese
• German
• Japanese
• Russian
• Italian