Operations24
Date
Selects the current date for the UPS display, YYYY-MM-DD
Time
Select the current time for the UPS display, HH:MM:SS
Display orientation
Selects the orientation of the display for use in rack or tower conguration. Options are:
• Auto-rotate = Automatically rotates based on the detected orientation of the UPS.
• Horizontal = Screen rotated for rack use.
• Vertical = Screen rotated for tower use.
Audible alarm
If enabled, the UPS will beep when an alarm is generated. If disabled, it will be silent.
• Enable (default)
• Disable
Change settings password
Opens the dialog to change the password used to access and update the UPS parameter settings.
System Parameter Options
Auto restart
Allows the automatic restart of the UPS when input power is restored after a complete shutdown of the
UPS system.
• Enable = The UPS will restart automatically when the input power is restored after a complete shut
down (default)
• Disable = The UPS will not restart automatically
Auto restart delay
Length of time to elapse before an automatic restart after input power is restored
• 0 - 999 seconds (default 0)
Start with no battery
Allows the UPS to start when the battery has reached the end of discharge (EOD). This can be used to
turn on the UPS and power the attached load without battery protection when utility power has been
restored after the battery was fully depleted. It works in conjunction with the Auto restart setting above.
• Enable (with Auto restart enable) = The UPS will power the load with no user intervention when
mains power returns after the battery has been fully depleted
• Enable (with Auto restart disabled) = The UPS will start up and allow the user to turn on the output
when power returns after the battery has been fully depleted
• Disable = The UPS cannot start with a fully depleted battery (default)