Vertiv | Liebert® EDGE | Installer/User Guide
25
Remote control
Allows the UPS to be controlled remotely via the CLI or SNMP card.
Enable (default)
Disable
Green function
The UPS will shut down automatically after180 minutes when the UPS is in battery mode and output
load is less than the value below.
OFF(default)
5%
10%
15%
IT system compatibility
When this option is enabled, the “Input phase reversed” and “Input ground lost” alarms are disabled.
Enable
Disable (default)
N-G Output Bond in Battery Mode
When this option is enabled, the output Neutral is connected to Ground when UPS is in battery mode.
Enable (default)
Disable
EPO logic
Select the EPO function control logic. Options are:
Active open = The UPS will activate the EPO function when Pin 1 and Pin 2 are open (default)
Active close = The UPS will activate the EPO function when Pin 1 and Pin 2 are closed (shorted)
Prog Outlets Parameter Options
Turn o outlet
Opens the dialog to turn o the programmable outlet.
Reboot outlet
Opens the dialog to turn on the programmable outlet.
Turn on delay
Sets the turnning on delay time of programmable outlet.
0 - 30 minutes (default of 0)