Vertiv | Liebert® EDGE | Installer/User Guide
25
Remote control
Allows the UPS to be controlled remotely via the CLI or SNMP card.
• Enable (default)
• Disable
Green function
The UPS will shut down automatically after180 minutes when the UPS is in battery mode and output
load is less than the value below.
• OFF(default)
• 5%
• 10%
• 15%
IT system compatibility
When this option is enabled, the “Input phase reversed” and “Input ground lost” alarms are disabled.
• Enable
• Disable (default)
N-G Output Bond in Battery Mode
When this option is enabled, the output Neutral is connected to Ground when UPS is in battery mode.
• Enable (default)
• Disable
EPO logic
Select the EPO function control logic. Options are:
• Active open = The UPS will activate the EPO function when Pin 1 and Pin 2 are open (default)
• Active close = The UPS will activate the EPO function when Pin 1 and Pin 2 are closed (shorted)
Prog Outlets Parameter Options
Turn o outlet
Opens the dialog to turn o the programmable outlet.
Reboot outlet
Opens the dialog to turn on the programmable outlet.
Turn on delay
Sets the turnning on delay time of programmable outlet.
• 0 - 30 minutes (default of 0)