Figure 6.8 Set alarms
High Room Air Temperature—Sets the threshold where a high room temperature alarm will occur, based
on the actual reading from either remote Sensor A or B. The range for the high room air temperature
alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C).
Low Room Air Temperature—Sets the threshold where a low room temperature alarm will occur, based on
the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is
from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C).
High Room Dewpoint—Sets the threshold where a high room dew point alarm will occur, based on the
calculated values from either remote Sensor A or remote Sensor B. The range for the high room dew point
alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold where a high refrigerant temperature alarm will occur
based on the actual reading from the supply refrigerant sensor. The supply refrigerant temperature is
from the Liebert XDC to the modules. The range for the high supply refrigerant temperature alarm is from
33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).