Break Value: Enter the value desired as the reference for the high current alarms (typically the rating of the breakers or
fuses fed by the shunt, if applicable).
High 1 Curr Limit Alarm: Enter the percentage value of the "Break Value" for alarm.
High 1 Curr Alarm Severity: Alarm level for this alarm. (See also Table 1 on page 2.)
High 1 Curr Alarm Relay: Select a relay number to map to this alarm.
“None” means there is no related relay number.
High 2 Curr Limit Alarm: Enter the percentage value of the "Break Value" for alarm.
High 2 Curr Alarm Severity: Alarm level for this alarm. (See also Table 1 on page 2.)
High 2 Curr Alarm Relay: Select a relay number to map to this alarm.
“None” means there is no related relay number.