NetSure
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
[163]
Break Value: Enter the value desired as the reference for the high current alarms (typically the rating of the breakers or
fuses fed by the shunt, if applicable).
High 1 Curr Limit Alarm: Enter the percentage value of the "Break Value" for alarm.
High 1 Curr Alarm Severity: Alarm level for this alarm. (See also Table 1 on page 2.)
High 1 Curr Alarm Relay: Select a relay number to map to this alarm.
“None” means there is no related relay number.
High 2 Curr Limit Alarm: Enter the percentage value of the "Break Value" for alarm.
High 2 Curr Alarm Severity: Alarm level for this alarm. (See also Table 1 on page 2.)
High 2 Curr Alarm Relay: Select a relay number to map to this alarm.
“None” means there is no related relay number.