Table 7. Contents of the Controller’s MIB
The name of the equipment manufacturer.
The manufacturers model designation of the power system.
identControllerFirmwareVersion
The firmware (software) version of the controller.
The name of the power plant. This object should be set by the administrator.
SNMP configuration version.
identControllerSerialNumber
Controller serial number.
Status of the complete plant (highest alarm). One of...
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
System voltage, stored as mV.
System current, stored as mA.
Used capacity, stored as percentage of the total capacity.
Battery voltage, stored as mV.
Battery current, stored as mA.
Calculated capacity, stored as % of the total capacity.
Nominal installed capacity, stored as mAh.