NetSure
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
[200]
<dirn>
This is the direction of the alarm condition. This parameter does not apply to this application. A <null> value is the only
value which is accepted for this parameter. If any other value is received for this parameter, an error response is returned
with the error code INUP.
<tmper>
This is the accumulation time period for PM parameters. This parameter does not apply to this application. A <null> value
is the only value which is accepted for this parameter. Other values for this parameter generate an error response using the
error code “INUP”.
Normal Response Format:
No response is returned if a valid User session has not been established. Otherwise the response is in the following format.
cr lf lf
^^^<source identifier>^<date>^<time> cr lf
M^^<ctag>^COMPLD [ <rspblk>] cr lf ;
<rspblk>
This is the response block which may be repeated multiple times.
cr lf
^^^”[<aid>][,<aidtype>]:<ntfcncde>,<condtype>,<srveff>, [<ocrdat>],[<ocrtm>],[<locn>],[<dirn>][,<tmper>]
[:[<conddescr>],[<aiddet>][,<obsdbhvr>[,<exptdbhvr>]] [:[<dgntype>][,<tblistl>]]]”
<aidtype>
This is the type of access identifier. Valid values for this application are:
EQPT equipment
If the command code modifier is ALL, <aidtype> is required to specify the type of access identifier, else <aidtype> may be
<null>.
<ntfcncde>
This is the notification code associated with a single alarm condition given in this block.
<condtype>
This is the condition type of the alarm condition being given in this block.
<srveff>
This is the effect on service caused by the single alarm condition given in this block.
<ocrdat>
This is the date when the triggering event occurred. The format for this parameter is MOY-DOM(Month-Of-Year - Day-Of-
Month). MOY ranges from 1 to 12 and DOM ranges from 1 to 31.
A <null> value for this parameter defaults to the current date unless <ocrtm> is <null>, then this parameter does not apply.
<ocrtm>
This is the time when the triggering event occurred. The format for this parameter is HOD-MOH-SOM (Hour-Of-Day -
Minute-Of-Hour - Second-Of-Minute). HOD ranges from 0 to 23. MOH and SOM range from 0 to 59.
A <null> value means this parameter and <ocrdat> are not applicable.

Table of Contents

Other manuals for Vertiv Netsure

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Netsure and is the answer not in the manual?

Vertiv Netsure Specifications

General IconGeneral
BrandVertiv
SeriesNetsure
Humidity Range5% to 95% non-condensing
Cooling MethodForced air
Communication InterfaceEthernet
Protection FeaturesOvervoltage, overcurrent, short circuit, overtemperature

Related product manuals